KUALITAS UDARA RUANG PERAWATAN PENYAKIT MENULAR DI RUMAH SAKIT PARU SURABAYA TAHUN 2016
Abstract
Infectious disease treatment rooms are places with a high risk of the transmission of diseases
and nosocomial infections. Therefore, there is a need for good environmental quality, either in terms of air
quality, and room construction condition, cleaning process and number of occupant density.
The study was a descriptive study aimed at describing the air quality of infectious disease
treatment rooms in Lung Hospital Surabaya in 2016. Data were collected by means of observations,
interviews, measurements and calculation of the airborne bacterial index.
CFU/m
3
Results showed that the airborne bacterial index of inpatient rooms was 1030 CFU/m
and >2628 CFU/m3 for Dahlia Room 1, Dahlia Room 2 and Pear Room, respectively. Room
temperature was 29.8
°
C, 30.5
°
C and 30.9C for Dahlia Room 1, Dahlia Room 2 and Pear Room,
respectively. Room humidity was 69%, 65% and 65% for Dahlia Room 1, Dahlia Room 2 and Pear Room,
respectively. Room air velocity was eligible for Dahlia Room 1 and Dahlia Room 2 at 0.49 m/s and 2 0.18
m/s respectively, but It was not so for Pear Room at 0.89 m/s. Room lighting was 62 lux, 26 lux and 81
lux for Dahlia Room 1, Dahlia Room 2 and Pear Room, respectively. In conclusion, the airborne bacterial
index, temperature, humidity and lighting in Lung Hospital Surabaya in 2016 did not meet the
requirements as defined in Decree of the Minister of Health No. 1204/Menkes/SK/X/2004 on Hospital
Environmental Health Requirements.
It iis recommended to improve the cleaning and maintenance process of those rooms in
accordance with health procedures and to improve construction of the rooms which do not meet the
requirements.
Keywords : Room air quality, Hospital
and nosocomial infections. Therefore, there is a need for good environmental quality, either in terms of air
quality, and room construction condition, cleaning process and number of occupant density.
The study was a descriptive study aimed at describing the air quality of infectious disease
treatment rooms in Lung Hospital Surabaya in 2016. Data were collected by means of observations,
interviews, measurements and calculation of the airborne bacterial index.
CFU/m
3
Results showed that the airborne bacterial index of inpatient rooms was 1030 CFU/m
and >2628 CFU/m3 for Dahlia Room 1, Dahlia Room 2 and Pear Room, respectively. Room
temperature was 29.8
°
C, 30.5
°
C and 30.9C for Dahlia Room 1, Dahlia Room 2 and Pear Room,
respectively. Room humidity was 69%, 65% and 65% for Dahlia Room 1, Dahlia Room 2 and Pear Room,
respectively. Room air velocity was eligible for Dahlia Room 1 and Dahlia Room 2 at 0.49 m/s and 2 0.18
m/s respectively, but It was not so for Pear Room at 0.89 m/s. Room lighting was 62 lux, 26 lux and 81
lux for Dahlia Room 1, Dahlia Room 2 and Pear Room, respectively. In conclusion, the airborne bacterial
index, temperature, humidity and lighting in Lung Hospital Surabaya in 2016 did not meet the
requirements as defined in Decree of the Minister of Health No. 1204/Menkes/SK/X/2004 on Hospital
Environmental Health Requirements.
It iis recommended to improve the cleaning and maintenance process of those rooms in
accordance with health procedures and to improve construction of the rooms which do not meet the
requirements.
Keywords : Room air quality, Hospital